Top Links
Tripp Lite - Tripp Lite SmartOnline 208/240V 20kVA On-Line UPS
Double Conversion, 18kW, N+1, 12U, Network Card Option, TAA Compliant - UPS (rack-mountable / external) - AC 200/208/240 V - 18 kW - 20000 VA - 1-phase 3 Wire - RS-232, USB - output connectors: 10 - 12U - 19" - TAA Compliant
Tripp Lite
SU20KRTAA
N/A
0037332223777
N/A
New
Product Description
Additional Details
What's Included
Main Specifications | |
---|---|
Product Description | Tripp Lite SmartOnline 208/240V 20kVA On-Line UPS - Double Conversion, 18kW, N+1, 12U, Network Card Option, TAA Compliant - UPS - 18 kW - 20000 VA |
Device Type | UPS - rack-mountable / external |
Rack Size | 19" - 12U |
Input Wiring | 1-phase 3 Wire |
Input Voltage | AC 200/208/240 V |
Output Voltage | AC 200/208/240 V ± 2% |
Power Capacity | 18 kW / 20000 VA |
Power Redundancy | Yes |
Input Connectors | Hardwire 3-wire |
Output connectors | 2 x power NEMA L6-30R ¦ 8 x power IEC 60320 C19 |
Run Time (Up To) | 4.3 min at full load |
Networking | RS-232, USB |
Remote Management Protocol | SNMP, Telnet, SSH |
TAA Compliant | TAA Compliant |
Manufacturer Warranty | 2-year warranty |
General | |
Device Type | UPS - rack-mountable / external |
Height (Rack Units) | 12U |
Rack Size | 19" |
Expansion / Connectivity | |
Interfaces | 1 x serial - 9 pin D-Sub (DB-9) ¦ 1 x EPO (emergency power off) ¦ 1 x USB |
Manufacturer Warranty | |
Service & Support | Limited warranty - 2 years |
Miscellaneous | |
Cables Included | USB cable ¦ Serial cable ¦ EPO cable |
Rack Mounting Kit | Included |
Equipment Protection Value | 250000 US Dollars |
Features | LCD display, LED indicators, built-in bypass switch, cold-start function, cooling fan, hot-swappable batteries, noise suppression |
Compliant Standards | CSA, UL 1778, RoHS, FCC Part 15 A, EMI, GSA, IEC 61000-4-5:1995 B |
TAA Compliant | Yes |
Networking | |
Remote Management Interface | RS-232, USB |
Remote Management Protocol | SNMP, Telnet, SSH |
Environmental Parameters | |
Min Operating Temperature | 32 °F |
Max Operating Temperature | 104 °F |
Humidity Range Operating | 0 - 95% (non-condensing) |
Sound Emission | 60 dBA |
Battery | |
Run Time (Up To) | 4.3 min at full load ¦ 12.5 min at half load |
Recharge Time | 6 hours |
Power Device | |
UPS Technology | On-line |
Power Redundancy | Yes |
Power Redundancy Scheme | N+1 |
Input Voltage | AC 200/208/240 V |
Frequency Provided | 50/60 Hz |
Input Wiring | 1-phase 3 Wire |
Frequency Required | 50/60 Hz |
Input Connectors | Hardwire 3-wire |
Power Output Connectors Details | 2 x power NEMA L6-30R ¦ 8 x power IEC 60320 C19 |
Output Voltage | AC 200/208/240 V ± 2% - 50/60 Hz |
Power Capacity | 18 kW / 20000 VA |
Output Waveform | Sinewave |
Circuit Protection | Circuit breaker |
Power Factor (PF) | 0.9 |
Dimensions & Weight (Shipping) | |
Shipping Width | 40.3 in |
Shipping Depth | 51 in |
Shipping Height | 36 in |
Shipping Weight | 601 lbs |